CAHIER AZUR – Performance investigation of SF6 free Gas Insulated DC Systems

Voir tous les articles de la revue

REE 2024-4
To reduce the CO2 emission of electricity generation and transmission, SF6 gas needs to be replaced by more environmentally friendly gas. A solution to replace SF6 in high voltage equipment is the mixture of Fluoronitrile CF3CN with CO2 and O2. In this paper, a choice of insulating gas based on theoretical analysis is mentioned including intrinsic gas properties and also CO2 footprint analysis. Experiments were then realized to verify the thermal and dielectric characteristics of gas mixture in the equipment. Finally, investigation tests were conducted with the actual SF6 design of GIS but filled with the mixture and showed very good performance. The results confirm the feasibility of using CF3CN-CO2-O2 mixture as insulating gas in HVDC GIS.

Société de l’Electricité, de l’Electronique et des Technologies de l’Information et de la Communication

17 rue de l’Amiral Hamelin  75116 Paris

Métro : « Boissière » Ligne 6 et « Iéna » Ligne 9

Téléphone : (+33) 1 56 90 37 17

N° de SIREN : 785 393 232, Code APE : 9412Z TVA intra-communautaire : FR44 785 393 232
×
×